Low-viscosity PCTFE inert oil. A mechanical seal barrier fluid and instrument fill fluid, as well as a single-phase immersion cooling / heat transfer fluid for electronics. It resists strong acids, strong bases, oxidizers and reactive gases (oxygen, chlorine), and is a cost-effective replacement for Solvay Galden HT230 — no flash point (nonflammable). Korea stock available, ready to ship.

TECHNICAL DATA

Technical data

Per HQ data. Product number 6.3 = kinematic viscosity (cSt) at 37.8°C (100°F).

Viscosity @ 37.8°C (100°F)6.3 cSt
Viscosity @ 40°C5.8 cSt
Density @ 25°C1.94 g/cm³
Pour point-71°C (-95°F)
Cloud point< -87°C
Dielectric constant2.8 ~ 3.0
Flash point / Fire pointNone (nonflammable)
Service temperature range-50 ~ +200°C
Max. safe operating temperature204°C (260°C short-term, clean system)
AppearanceColorless clear liquid (Water White)
Chemical familyPCTFE

※ Detailed cooling-design properties such as thermal conductivity, boiling point and dielectric strength (kV/mm) are provided from the latest HQ datasheet — inquire below.

Galden replacement
Halocarbon 6.3 → Galden HT230

Per HQ data, 6.3 Oil is comparable to Galden HT230 in vapor pressure and viscosity, and while it holds similar thermal conductivity and boiling point, its dielectric strength and dielectric constant are superior to Galden. Higher in viscosity than 4.2, it suits systems that require boiling margin and film stability.

A dielectric constant of 2.8–3.0 insulates electronic components to reduce the risk of short circuits, and long-term thermal stability to 204°C gives the fluid a long service life even in high-heat environments. It stays chemically inert even in contact with strong acids, oxidizers and reactive gases.

COOLING & HEAT TRANSFER

Single-phase immersion cooling · heat transfer fluid

Halocarbon 4.2 and 6.3 are the fluids HQ presents with properties optimized for single-phase immersion cooling. For two-phase (evaporative) immersion cooling, HFMOP is the fit.

  • Data-center / HPC electronics immersion cooling — nonflammable and inert, dielectric constant 2.8–3.0
  • Semiconductor process thermal management — temperature control for etch, ion implantation and more
  • Vapor Phase Soldering (VPS) — uniform heating
  • Electronics reliability testing — thermal-shock and burn-in baths
  • Mechanical seal barrier fluid — isolating reactive media
  • Instrument fill fluid — gauges, pressure sensors, diaphragm seals
  • Hazardous processes — strong acids, strong bases, flammable solvents, corrosive chemicals
  • Oxygen / chlorine service — reactive-gas environments
SERIES POSITION

Position within the series — choosing Halocarbon Oil by viscosity

6.3 is in the low-viscosity line. If you need a fluid with faster circulation and cooling cycles, consider 4.2; if you need a medium viscosity for compressors or hydraulics, consider 27.

GradeViscosity (cSt @37.8°C)Pour pointTypical applications
0.80.8-129°CCryogenic calibration bath · refrigeration
4.24.2-73°CSingle-phase immersion cooling · instrument fill · seal (Galden HT230)
6.36.3-71°CSingle-phase immersion cooling · seal barrier (Galden HT230)
2727-40°CCompressor · hydraulic fluid · vapor phase soldering
5656-34°CCompressor · general bearings
9595-26°CInstrument fill · general-purpose inert lubrication
200 ~ 1000N200 ~ 1000-12 ~ +10°CMedium to maximum-load bearings & gearboxes
KOREA STOCK AVAILABLE

Korea stock available — request a quote, sample, or datasheet

For immersion-cooling / heat-transfer applications, tell us your system conditions (heat load, flow rate, target temperature, materials); for seal / fill applications, tell us the equipment model, and we will reply within 24 business hours with the optimal grade and a quote. Genuine HQ product supplied direct, with batch traceability.